The LIOB‑586/587/588/589 I/O Controllers are IP-enabled, compact, programmable automation stations for LonMark Systems and BACnet/ IP networks with physical inputs and outputs and integrated graphical visualization.
Communication
The LIOB‑586/587/588/589 I/O Controllers are equipped with two Ethernet ports including a built-in Ethernet switch. This allows for building a daisy chained line topology of up to 20 devices, which reduces costs for network installation. Dual Ethernet port devices also allow the setup of a redundant Ethernet installation (ring topology), which increases reliability. The redundant Ethernet topology is enabled by the Rapid Spanning Tree Protocol (RSTP), which is supported by most managed switches.
Technology data points are automatically exposed as OPC tags for higher level OPC client applications or L‑WEB system via the integrated OPC server providing SSL encrypted web services (OPC XML‑DA) or UA Secure Conversation (OPC UA). The L‑IOB I/O Controllers further allow data exchange over global connections (network-wide data exchange), offer AST™ functions (Alarming, Scheduling, and Trending), store custom graphic pages for visualization in LWEB‑802/ 803, and can be seamlessly integrated in the LWEB‑900 Building Management System. LIOB‑586/587/588/589 I/O Controllers implement the BACnet Building Controller (B-BC) profile and are BTL certified.
IoT Integration
The IoT function (Node.js) allows connecting the system to almost any cloud service, either for uploading historical data to analytics services, delivering alarm messages to alarm processing services or operating parts of the control system over a cloud service (e.g., scheduling based on Web calendars or booking systems). Processing Internet information such as weather data in forecast-based control is also possible. Finally, the JavaScript kernel also allows implementing serial protocols to non-standard equipment in primary plant control.
Local Operation and Override
All L‑IOB I/O Controllers are equipped with an LCD-display (128×64) with backlight and jog dial for manual local operation and override. Device and data point information is displayed in text form and via graphical symbols. On the LIOB‑586 /LIOB-587 front panel the six relay outputs can be overridden via 3-way switches.
Power Measurement
External meters can be integrated via M‑Bus or Modbus. The LIOB‑586/587/588/589 I/O Controllers perfectly meet energy management and energy reporting applications. The LIOB‑587 includes built-in power measurement.
Features
- Automation station with physical inputs and outputs
- Programmable with L‑STUDIO (IEC 61131‑3 or IEC 61499)
- Room controller for up to 2 room segments
- Extension with physical inputs and outputs using one L‑IOB I/O Module (LIOB‑11x or LIOB‑45x/55x)
- 128×64 graphic display with backlight
- Local and remote access to information about device status and data points
- Manual operation using the jog dial or VNC client
- Manual override of each output through switches (LIOB-586 only)
- Alarming, Scheduling, and Trending (AST™)
- Node.js support* for easy IoT integration (e.g. Google calendar, Alexa & friends, multimedia equipment, …)
- Event-driven e-mail notification
- Math objects to execute mathematical operations on data points
- Stores customized graphical pages
- Visualization of customized graphical pages through LWEB‑900 (Building Management), LWEB‑803 (Monitoring and Control), or LWEB‑802 (Web Browser)
- Support of the L‑STAT Room Operator Panel
- Built-in OPC XML‑DA and OPC UA server
- Dual Ethernet/IP interface
- Access to network statistics
- Compliant with ANSI/ASHRAE 135‑2012 and ISO 16484‑5:2012 standard
- Supports BACnet MS/TP, BACnet/IP or BACnet/SC
- BACnet Client Function (Write Property, Read Property, COV Subscription)
- BACnet Client Configuration with configuration tool (scan and EDE import)
- B-BC (BACnet Building Controller) functionality, BTL certified
- Compliant with CEA‑709, CEA‑852, and ISO/IEC 14908 Standard (LonMark System)
- Supports IP‑852 (Ethernet/IP)
- Support of dynamically created or static NVs
- Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)
- Integrated BACnet/ IP to BACnet/SC and BACnet MS/ TP Router including BBMD as well as Slave-Proxy functionality
- M‑Bus Master according to EN 13757‑3, connection via optional M‑Bus Converter (L‑MBUS20 or L‑MBUS80)
- Gateway functions including Smart Auto-Connect™
- Modbus TCP and Modbus RTU (Master or Slave)
- Integrated web server for device configuration and monitoring data points
- Connection to EnOcean wireless devices via LENO‑80x Interface
- Supports WLAN through LWLAN‑800 Interface
- Supports MP-Bus through LMPBUS-804 Interface
- Supports LTE through LTE‑800 Interface
- Stores user-defined project documentation
- Supports VPN
*requires L-IOT1 software license
LIOB-586/587/588/589 I/O Controller Products
LIOB-586
L-IOB I/O Controller: 6 UI, 4 DI, 6 DO (6 x Relay 10 A Type2)
LIOB-587
I/O Controller, 6 UI, 4 DI, 6 DO (6 x Relay 10 A Type2), 6 channel power measurement built-in
LIOB-588
L‑IOB I/O Controller: 10 UI, 6 AO, 8 DO (8 x Relay 6 A)
LIOB-589
L‑IOB I/O Controller: 10 UI, 6 AO, 6 DI, 4 DO (4x Relay 6 A)
L-IOT1
Add-on Software License to enable IoT functionality on LIOB-585/586/587/588/589, LIOB-590/591/592/593/594/595/596, LIOB-AIR, and LINX-102/103/202/203
L-STUDIO
Device configuration and programming suite
LPOW-2415A
LIOB-Connect Power Supply, 24 VDC, 15 W
LPOW-2415B
Power supply unit with power connector 24 VDC, 15 W
L-TEMP2
External temperature sensor (NTC10K) for use with L-IOB Universal Inputs
LENO-800
EnOcean Interface 868 MHz Europe
LENO-801
EnOcean Interface 902 MHz USA/Canada
LENO-802
EnOcean Interface 928 MHz Japan
LWLAN-800
Wireless LAN Interface IEEE 802.11bgn
LTE-800
LTE Interface
LMPBUS-804
MP-Bus Interface for 16 devices per channel, up to 4 channels
L-MBUS20
M-Bus level converter, interface for 20 M-Bus devices
L-MBUS80
M-Bus Level Converter, Interface for up to 80 M-Bus devices
LRS232-802
USB to 2x RS-232 Interface
LOYREL-816
Relay Interface, 8 x Digital Output 16 A Relays, 8 x Digital Input 0/10 V
LOYCNV-VA8
Voltage / Current Converter, 8 channels, 0-10 V input to 4-20 mA output converter
L-TRIAC16
TRIAC Interface, 16 x Digital Output 0.5 A TRIAC, 16 x Digital Input (0/10 V)
LSTAT-810-GX-LX-CU
LSTAT-800 based custom design, includes EnOcean interface, minimum quantity 100 pcs, enclosure G1: silver, G2: black, G3: white; custom print Lx, including 2 working samples, lead time 10 weeks (needs LSTAT-80x-CUSTOM)
LSTAT-812-GX-LX-CU
LSTAT-802 based custom design, includes EnOcean interface, minimum quantity 100 pcs, enclosure G1: silver, G2: black, G3: white; custom print Lx, including 2 working samples, lead time 10 weeks (needs LSTAT-80x-CUSTOM)
LSTAT-80x-CUSTOM
One-time customization cost for L-STAT custom design, including 2 working samples
LIOB-100
LIOB-Connect I/O Module: 8 UI, 2 DI, 2 AO, 9 DO (5 x Relay 6 A, 4 x Triac 0.5 A)
LIOB-101
LIOB-Connect I/O Module: 8 UI, 16 DI
LIOB-102
LIOB-Connect I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)
LIOB-103
LIOB-Connect I/O Module: 6 UI, 6 AO, 5 DO (5 x Relay 16 A)
LIOB-110
LIOB-Connect I/O Module: 20 Universal I/O (IO)
LIOB-112
LIOB‑Connect I/O Module: 40 Universal I/O (12 optionally with 4-20 mA Current Output)
LIOB-IP852 I/O Module: 8 UI, 2 DI, 2 AO, 8 DO (4 x Relay 6 A, 4 x Triac 0.5 A)
LIOB-451
LIOB-IP852 I/O Module: 8 UI, 12 DI
LIOB-452
LIOB-IP852 I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)
LIOB-453
LIOB-IP852 I/O Module: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)
LIOB-454
LIOB-IP852 I/O Module: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor
LIOB-551
LIOB-BIP I/O Module: 8 UI, 12 DI
LIOB-552
LIOB-BIP I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)
LIOB-553
LIOB-BIP I/O Module: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)
LIOB-554
LIOB-BIP I/O Module: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor
LIOB-560
LIOB-BIP I/O Modul: 20 Universal I/O (IO)
LIOB-562
LIOB-BIP I/O Module: 40 Universal I/O (12 optionally with 4-20 mA Current Output)